96
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Figure 46. REPO Terminal Block Connector Assignments
EPO_A_B
GND-ISO
UPS REPO
1 2 3 4
EPO_A
EPO_B
Normally Closed
REPO Contacts
Normally Open
REPO Contacts
Table 27. Normally-Open REPO Connections and Wire Terminations
From REPO
Station
Switch Con-
tact Block
(Either
Block)
UPS
REPO
Termi-
nal
Nam-
e
Description
Recommended
Minimum
Wire Size
Size of
Wire
Termination
Tightening
Torque
3 NO
3
EPO_
A
Input: Normally-open dry
contact used to activate UPS
EPO from a remote switch
Twisted Pair Wires
#18 AWG
#16
#30 AWG
2 lb in
(0.22-0.25 Nm)
4 NO
4
EPO_
B
Figure 47. Normally-Open REPO Switch Wiring
3
1
2
4
3
4
REPO
Switch
(NO)
Twisted
Wires
REPO TB