58
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
6.
Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately
3 mm (1/8").
7.
Remove the hardware loosened in
Step 4
.
8.
If a sidecar is attached to the UPS, remove the hardware loosened in
Step 5
.
9.
Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle
the pallet skids and hardware in a responsible manner.
CAUTION
CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
must be lowered by the jacking bolts before the supports can be removed. If unpacking and unloading
instructions are not closely followed, the cabinet may tip and cause serious injury or death.
10. Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two full turns
(maximum)
until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.
11. After the UPS is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
responsible manner.
12. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together and remove
the side supports.
13. If a sidecar is attached to the UPS, loosen the bottom screws and completely remove the top screws
securing the sidecar front panel. Lift the panel straight up to remove the panel.
14. If a sidecar is attached to the UPS, remove the sidecar mounting bolts holding the front and rear sidecar
supports to the cabinet base.
15. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base.
16. If installing the cabinet permanently, retain the cabinet mounting bolts; otherwise, recycle the bolts along
with the support brackets in a responsible manner.
17. Close the door and secure the latch.
18. If a sidecar is attached to the UPS, remove the screws securing sidecar rear shipping bracket. Remove the
bracket and reinstall the screws (see
).
19. If the leveling feet are not retracted, turn all leveling feet until they are retracted as far into the cabinet as
possible.
CAUTION
To prevent tipping when rolling the cabinet, push the cabinet from the rear whenever possible.
20. Roll the cabinet to the final installation location.
21. Lower the UPS cabinet feet and using a level, adjust the cabinet height accordingly until the cabinet is
level.
NOTE
An optional front and rear floor mounting bracket kit is available for permanently
mounting the UPS.
22. If permanently mounting the UPS using the customer supplied left and right side floor mounting brackets,
proceed to
Step 23
; if using the optional front and rear floor mounting bracket kit, proceed to
Step 27
;
otherwise, proceed to
Step 30
.
23. Locate the customer supplied left and right side floor mounting brackets and hardware.