108
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Figure 54. Eaton 93PM-L 60 UPS System Oneline
UPM 2
UPM 1
FUSE
UPS CABINET
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
OPTIONAL
SINGLE-FEED
JUMPER
AC INPUT TO
RECTIFIER
AC INPUT TO
BYPASS
(SEE NOTE 3)
EXTERNAL
BATTERY
CABINET
BATTERY
BREAKER
AC OUTPUT
TO
LOAD
STATIC
SWITCH
FUSE
E1,E2,E3
E6,E7,
E8,E12
E9,E10,
E11,E12
E4,E5
NOTES:
1. AC INPUT TO RECTIFIER IS NOT USED IN SINGLE FEED CONFIGURATION.
2. DASHED LINES INSIDE OF UPS INDICATE OPTIONAL UPM'S OR INTERNAL
BATTERIES. CONFIGURABLE FROM 1-3 UPMS.
3. DASHED LINES OUTSIDE OF UPS INDICATE OPTIONAL EQUIPMENT CABINETS.
4. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER
SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED.
FUSE
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
UPM 3
FUSE
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
CB2 BATT
BREAKER
INTERNAL
BATTERY
4 STRINGS MAX
C
D
A
B