Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
49
Table 18. Recommended Output Circuit Breaker Ratings
Output Rating
UPS Model
UPS Rating
Load Rating
208V
220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
10 kW
80% Rated
35A
35A
100% Rated
30A
30A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
20 kW
80% Rated
70A
70A
100% Rated
60A
60A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
30 kW
80% Rated
110A
100A
100% Rated
90A
80A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
40 kW
80% Rated
150A
150A
100% Rated
125A
110A
Eaton 93PM-L 60-3
50 kW
80% Rated
175A
175A
100% Rated
150A
150A
Eaton 93PM-L 60-3
60 kW
80% Rated
225A
200A
100% Rated
175A
175A
There is no manual DC disconnect device within the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed based on 2 volts per cell.
If required, external DC input overcurrent protection and disconnect switch is to be supplied by the customer.
lists the recommended ratings for circuit breakers satisfying the criteria for each battery voltage.
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer
discharge times a larger disconnect may be required.
Table 19. Recommended DC Input Battery Disconnect Circuit Breaker Ratings
Output Rating
UPS Model
UPS Rating
208V or 220V
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
10 kW
25A
Eaton 93PM-L 60-1
Eaton 93PM-L 60-2 (N+1)
20 kW
45A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
30 kW
70A
Eaton 93PM-L 60-2
Eaton 93PM-L 60-3 (N+1)
40 kW
90A
Eaton 93PM-L 60-3
50 kW
125A
Eaton 93PM-L 60-3
60 kW
150A