Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
95
44..66..66
IInnssttaalllliinngg M
Miinniisslloott IInntteerrffaaccee C
Coonnnneeccttiioonnss
NOTE 1
LAN drop for use with Minislot cards must be provided by the customer.
NOTE 2
When installing interface wiring connections, conduit must be installed between each
device and the UPS cabinet.
NOTE 3
Remove the cabinet stiffener bar (see ) before installing or removing Minislot cards.
Reinstall the bar after the procedure is completed.
For installation and setup of a Minislot card, contact an Eaton service representative (see paragraph
To install wiring:
1.
If not already installed, install the LAN drop.
2.
If not already opened, open the front door by lifting the latch from the bottom and turning to the right
(counterclockwise) and swing the door open.
3.
If wiring a Minislot card from the bottom of the UPS, proceed to
; otherwise, proceed to
.
4.
Remove the top interface entry conduit landing plate to drill or punch holes (see
).
5.
Reinstall the interface entry plate and install the conduit.
6.
Top Entry Wiring.
Route the Minislot card interface wiring through the top interface entry conduit landing
plate to the Minislot card terminals. See
for wiring access information, and
for Minislot
card locations.
7.
Proceed to
8.
Remove the bottom interface entry conduit landing plate to drill or punch holes (see
).
9.
Reinstall the interface entry plate and install the conduit.
10.
Bottom Entry Wiring.
Route the Minislot card interface wiring through the bottom interface entry conduit
landing plate to the bottom access interface wiring channel along the inside of the front door (see
).
11. Route the wiring along the interface wiring channel to the Minislot card terminals. See
for
Minislot card locations.
12. Secure the wiring to the wire tie anchors provided (see
) using Zip ties.
13. Install the LAN and other cables to the appropriate Minislot cards. Refer to the manual supplied with the
Minislot card for terminal assignments.
14. Refer to the manual supplied with the Minislot card for operator instructions.
15. If wiring REPO connections, proceed to paragraph
; otherwise, proceed to
16. Close the UPS outside door and secure the latch.
44..77
IInnssttaalllliinngg aa R
REEP
PO
O S
Sw
wiittcchh
A latching-type Remote Emergency Power-off (REPO) switch can be used in an emergency to shut down the
UPS and remove power to the critical load from a location away from where the UPS is installed. shows a
REPO switch.