146
Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Model (50 or 60 Hz)
Power Rating
Model (50 or 60 Hz) [
Continued
]
Power Rating
Eaton 93PM-L 200-5
Eaton 93PM-L 200-6 (N+1)
95 kW
Eaton 93PM-L 200-10
195 kW
Eaton 93PM-L 200-5
Eaton 93PM-L 200-6 (N+1)
100 kW
Eaton 93PM-L 200-10
200 kW
Eaton 93PM-L 200-6
Eaton 93PM-L 200-7 (N+1)
105 kW
99..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
99..22..11
U
UP
PS
S IInnppuutt
Operating Input Voltage
Rectifier: 208 or 220 Vac Wye, 3W + ground. Neutral not used.
Bypass: 208 or 220 Vac Wye, 4W + ground.
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
through
.
Reduced for Generator
Adjustable
Input Current Harmonic Content
≤ 3.5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Battery Voltage
240 cell – 480Vdc
Battery Charging Capacity
7 A maximum per 20 kW module at full load at nominal input voltage
99..22..22
U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Output Voltage
208 or 220 Vac Wye, 3W or 4W + ground
Output Voltage Harmonic Content
< 1.6% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
through
.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
< 2.5° for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
1 Hz per second (default setting)