Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
147
Load Compatibility
0.8 pF Leading
0.8 pF Lagging
Overload Capability
<110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
99..22..33
U
UP
PS
S EEnnvviirroonnm
meennttaall
Operating Temperature
5 to 40° C (41 to 104° F) without derating. The recommended operating temperature
is 25° C (77 °F).
Operating Altitude
Maximum 1500m (5000 ft) at 40° C without derating
Storage Temperature
-25 to +55° C, excluding batteries (prolonged storage above 40° C causes rapid
battery self-discharge)
Relative Humidity (operating and
storage)
5 to 95%, noncondensing
Acoustical Noise
200 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779
Agency Markings
Safety: UL1778 5th Ed./CSA22.2 No. 107.3–14 3rd Ed.
EMI Emissions
Meets IEC 62040-2 C2, CISPR 22, VCCI and FCC Part 15 Subpart B Class A limits.
Immunity / Electrostatic Discharge
(ESD)
Meets IEC 61000-4-2 Level 3 specifications and CISPR 24. Withstands up to 4 kV
contact pulse without damage and with no disturbance or adverse effect to the
critical load.
Summary of Contents for 93PM-L IAC-B