Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
37
Table 12. Input/Output Ratings and Wiring Recommendations: 160–200 kW (220/220)
Basic Unit Rating
Units
Rating 50/60 Hz
kW
160
170
180
190
200
Input and Output Voltage
Volts
220/220
220/220
220/220
220/220
220/220
AC Input to UPS Rectifier (0.99
Minimum pF)
Full load current plus battery recharge
current
(3) Phases, (1) Ground
A
Amps
537
571
605
638
672
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
250 MCM
(3)
300 MCM
(3)
350 MCM
(3)
350 MCM
(3)
500 MCM
(3)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
2
(3)
2
(3)
2
(3)
2
(3)
1/0
(3)
AC Input to UPS Bypass (Four Wire,
Dual-Feed)
Full Load Current: (3) Phases– see
Note, (1) Ground
B
Amps
537
571
605
638
672
Neutral Current
Amps
727
773
818
864
909
Minimum Conductor Size (Phase A, B,
and C)
Number per Phase
AWG or
kcmil
(each)
400 MCM
(3)
500 MCM
(3)
500 MCM
(3)
500 MCM
(3)
500 MCM
(4)
Neutral Wire Size
Number
AWG or
kcmil
(each)
4/0
(6)
250 MCM
(6)
300 MCM
(6)
300 MCM
(6)
4/0
(8)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
1/0
(3)
1/0
(3)
1/0
(3)
1/0
(3)
1/0
(4)
DC Input from External Battery (Line-Up-and-Match Eaton 93PM-L IBC-SW, IBC-LW or IBC-LHW)
For Line-Up-and-Match wiring refer to
Eaton 93PM Integrated Battery Cabinet Installation Manual-Small Welded
or
Eaton 93PM
Universal Integrated Battery Cabinet Installation Manual-Large and Large High Rate
DC Input from External Battery
(Standalone Eaton 93PM-L IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total
Amps
361
384
407
429
452
Minimum Conductor Size (Phase
Positive and Negative)
Number per Pole
AWG or
kcmil
(each)
4/0
(2)
4/0
(2)
250 MCM
(2)
250 MCM
(2)
300 MCM
(2)
Minimum Conductor Size (Ground)
Number
–
AWG or
kcmil
(each)
2
(2)
2
(2)
2
(2)
2
(2)
2
(2)