56
Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Table 21. Recommended Input and Bypass Circuit Breaker Ratings (Continued)
Input Rating
UPS Model
UPS Rating
Load Rating
208V
220V
Eaton 93PM-L 200-8
Eaton 93PM-L 200-9 (N+1)
150 kW
80% Rated
700A
700A
100% Rated
600A
600A
Eaton 93PM-L 200-8
Eaton 93PM-L 200-9 (N+1)
160 kW
80% Rated
800A
700A
100% Rated
600A
600A
Eaton 93PM-L 200-9
Eaton 93PM-L 200-10 (N+1)
170 kW
80% Rated
800A
800A
100% Rated
700A
600A
Eaton 93PM-L 200-9
Eaton 93PM-L 200-10 (N+1)
180 kW
80% Rated
800A
800A
100% Rated
700A
700A
Eaton 93PM-L 200-10
190 kW
80% Rated
1000A
800A
100% Rated
700A
700A
Eaton 93PM-L 200-10
200 kW
80% Rated
1000A
1000A
100% Rated
800A
700A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with the NEC, ANSI/NFPA 70.