Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
69
WARNING
Do not remove or loosen the cabinet mounting or cabinet support bolts until instructed
4.
Loosen, but do not remove, the skid mounting bolts holding the pallet skids to the front and rear supports,
and to the left and right side supports (see
, or
and
).
WARNING
RISK OF INSTABILITY. Turning the jacking bolts unevenly may cause the cabinet to become unbalanced. To
prevent tipping the cabinet, raise and lower the jacking bolts evenly.
CAUTION
CABINET MAY TIP. Raise the UPS no more than 3 mm (1/8") above the floor (just enough to allow the removal
of the pallet skids).
5.
Turn each jacking bolt consecutively, two full turns, until the pallet skids clear the floor by approximately
3 mm (1/8").
6.
Remove the hardware loosened in
7.
Pull the pallet skids out from under the metal angle supports without disturbing the jacking bolts. Recycle
the pallet skids and hardware in a responsible manner.
CAUTION
CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
must be lowered by the jacking bolts before the supports can be removed.
8.
Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two full turns
(maximum)
until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.
9.
After the UPS is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
responsible manner.
10. Remove the cabinet support bolts fastening the front, rear, and side cabinet supports together and remove
the side supports (see
, or
and
11. Remove the cabinet mounting bolts holding the front and rear supports to the cabinet base (see
or
and
12. If installing the cabinet permanently, retain the cabinet mounting bolts; otherwise, recycle the bolts along
with the support brackets in a responsible manner.
13. Close the door and secure the latch.
14. If the Two Pallet Shipment configuration was utilized, go to
and perform the steps outlined to
remove the Pallet from the Wireway.
15. If the leveling feet are not retracted on the UPS, turn all four leveling feet until they are retracted as far into
the cabinet as possible.
CAUTION
To prevent tipping when rolling the cabinet, push the cabinet from the rear whenever possible.
16. Roll the cabinet and Wireway, if applicable, to the final installation location.
Summary of Contents for 93PM-L IAC-B
Page 162: ...16400072401 164000724 01 ...