Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
Figure 40. Eaton 93PM-L 200 UPS System Oneline
NOTES:
1. AC INPUT TO RECTIFIER IS NOT USED IN SINGLE FEED CONFIGURATION.
2. DASHED LINES INDICATE OPTIONAL UPM'S. CONFIGURABLE FROM 1-10 UPMS.
3. BACKFEED PROTECTION IS NOT PROVIDED AS A PART OF UPS. CUSTOMER
SUPPLIED BYPASS INPUT BREAKER WITH 48-60VDC SHUNT TRIP IS REQUIRED.
UPMs 2-10
UPM 1
FUSE
UPS CABINET
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
OPTIONAL
SINGLE-FEED
JUMPER
AC INPUT TO
RECTIFIER
AC INPUT TO
BYPASS
(SEE NOTE 3)
EXTERNAL
BATTERY
CABINET
BATTERY
BREAKER
AC OUTPUT
TO
LOAD
STATIC
SWITCH
FUSE
E1,E2,E3
E6,E7,
E8,E12
E9,E10,
E11,E12
E4,E5
FUSE
BATTERY
SWITCHGEAR
BATTERY
CONVERTER
FUSE
FUSE
RECTIFIER
INVERTER
RECTIFIER
SWITCHGEAR
INVERTER
SWITCHGEAR
A
B
D
C