Eaton 93PM-L 20–200kW (208V) UPS Installation and Operation Manual 164000724—Rev 01
57
The line-to-line unbalanced output capability of the UPS is limited only by the full load per phase current values
for AC output to critical load shown in
through
. The recommended line-to-line load unbalance
is 50% or less.
Bypass and output overcurrent protection and bypass and output disconnect switches are to be supplied by the
customer.
lists the recommended rating for output circuit breakers.
Table 22. Recommended Output Circuit Breaker Ratings
Output Rating
UPS Model
UPS Rating
Load Rating
208V
220V
Eaton 93PM-L 200-1
Eaton 93PM-L 200-2 (N+1)
10 kW
80% Rated
35A
35A
100% Rated
30A
30A
Eaton 93PM-L 200-1
Eaton 93PM-L 200-2 (N+1)
20 kW
80% Rated
70A
70A
100% Rated
60A
60A
Eaton 93PM-L 200-2
Eaton 93PM-L 200-3 (N+1)
30 kW
80% Rated
110A
100A
100% Rated
90A
80A
Eaton 93PM-L 200-2
Eaton 93PM-L 200-3 (N+1)
40 kW
80% Rated
150A
150A
100% Rated
125A
110A
Eaton 93PM-L 200-3
Eaton 93PM-L 200-4 (N+1)
50 kW
80% Rated
175A
175A
100% Rated
150A
150A
Eaton 93PM-L 200-3
Eaton 93PM-L 200-4 (N+1)
60 kW
80% Rated
225A
200A
100% Rated
175A
175A
Eaton 93PM-L 200-4
Eaton 93PM-L 200-5 (N+1)
70 kW
80% Rated
250A
250A
100% Rated
200A
200A
Eaton 93PM-L 200-4
Eaton 93PM-L 200-5 (N+1)
80 kW
80% Rated
300A
300A
100% Rated
225A
225A
Eaton 93PM-L 200-5
Eaton 93PM-L 200-6 (N+1)
90 kW
80% Rated
350A
300A
100% Rated
250A
250A
Eaton 93PM-L 200-5
Eaton 93PM-L 200-6 (N+1)
100 kW
80% Rated
350A
350A
100% Rated
300A
300A
Eaton 93PM-L 200-6
Eaton 93PM-L 200-7 (N+1)
110 kW
80% Rated
400A
400A
100% Rated
350A
300A
Eaton 93PM-L 200-6
Eaton 93PM-L 200-7 (N+1)
120 kW
80% Rated
450A
400A
100% Rated
350A
350A
Eaton 93PM-L 200-7
Eaton 93PM-L 200-8 (N+1)
130 kW
80% Rated
500A
450A
100% Rated
400A
350A
Eaton 93PM-L 200-7
Eaton 93PM-L 200-8 (N+1)
140 kW
80% Rated
500A
500A
100% Rated
400A
400A