Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
1.
Transfer the critical load to bypass by performing the procedure in paragraph
Transfer from Double Conversion to Bypass Mode
2.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
3.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
4.
On the UPM Select screen, select UPM 1. The UPM Control Screen is displayed.
5.
Tap the
SHUT DOWN MODULE
button.
The UPM status indicates SHUTDOWN. The power module is turned off.
Logic power remains on.
6.
Repeat
Steps 2
through
Step 5
selecting UPM 2 to shut down UPM 2.
The UPM status indicates SHUTDOWN. The power module is turned off.
Logic power remains on.
7.
Repeat
Steps 2
through
Step 5
selecting UPM 3 to shut down UPM 3.
The UPM status indicates SHUTDOWN. The power module is turned off.
Logic power remains on.
66..33..1100 S
Siinnggllee U
UP
PM
M S
Shhuuttddoow
wnn
To shut down a single UPM:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
3.
On the UPM Select screen, select the UPM to shutdown. The UPM Control Screen is displayed.
4.
Tap the
SHUT DOWN MODULE
button.
The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to
supply the critical load.
Logic power remains on.
66..33..1111 S
Siinnggllee U
UP
PM
M R
Reessttaarrtt
To restart a single UPM from a shutdown state:
1.
Tap the
CONTROLS
tab on the main menu navigation bar. The System Control screen is displayed.
2.
Tap the
MODULES CONTROLS
tab on the secondary Control menu navigation bar. The UPM Select
screen is displayed.
3.
On the UPM Select screen, select the UPM to start. The UPM Control Screen is displayed.
4.
Tap the
START MODULE
button.
The UPM rectifier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer
to the Double Conversion mode and supply the critical load.
66..33..1122 U
UP
PS
S aanndd C
Crriittiiccaall LLooaadd S
Shhuuttddoow
wnn
To perform maintenance or service on the critical load, shut down power to the load:
1.
Turn off all equipment that is being powered by the UPS.
2.
Perform the Load Off procedure in paragraph
Using the UPS LOAD OFF Command
.