Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
5
11..22..22
S
Siiddeeccaarr IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--B
Byyppaassss
A Sidecar Integrated Accessory Cabinet-Bypass (SIAC-B) provides maintenance bypass functions. The SIAC-B
is available in two, three, or four breaker configurations enabling power to completely bypass the UPS. The
UPS can then be safely serviced or replaced without interrupting power to critical systems. Our manufacturing
facility installs the SIAC-B on either the right or left side of the UPS cabinet based on the order requirements.
The SIAC-B can also be used for top entry wiring access.
11..22..33
TToopp EEnnttrryy W
Wiirriinngg S
Siiddeeccaarr
If required, a sidecar is available for top entry power wiring. The sidecar performs the function of a wireway
routing the wires to the terminals mounted at the bottom of the UPS cabinet. The sidecar can be installed on
the left or right side of the UPS cabinet.
11..22..44
IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--P
Poow
weerr D
Diissttrriibbuuttiioonn
The Integrated Accessory Cabinet-Power Distribution (IAC-PD) provides power distribution options for servers,
racks, and other equipment via distribution panelboards, or distributes power to larger loads via distribution
subfeed circuit breakers. The distribution options are customer configurable, enabling adaptation and expansion
without costly electrical rework. The IAC-PD may be installed in a line-and-match or standalone configuration.
The IAC-PD may be installed on either the right or left side of the UPS cabinet.
11..22..55
P
Paarraalllleell S
Syysstteem
m
NOTE
All UPSs in a parallel system must have the same battery configuration. Each UPS
requires a separate battery cabinet.
A parallel UPS system with multiple UPSs with a maximum combined wattage of 400 kW can be installed to
provide a parallel capacity and/or redundant system. This load sharing system provides more capacity than a
single UPS, and can provide redundancy, depending on the load and configuration. In addition, when one UPS
is taken out of service for maintenance or is not operating properly, a redundant UPS continues to supply
uninterrupted power to the critical load. A built-in Controller Area Network (CAN) provides connectivity for
system metering and operational mode control. The parallel system consists of two to four UPSs, and a Wall
Mounted Panelboard acting as a tie point and to control the output.
11..22..66
M
Moonniittoorriinngg aanndd C
Coom
mm
muunniiccaattiioonn
Minislot Cards
– Optional Minislot cards support several protocols, such as SNMP, SMTP, HTTP, Modbus
®
,
and TCP/IP. See
, for additional information on monitoring and communication
features.
Remote Monitoring Device (RMD)
– An optional RMD contains a touch screen status display and a local
audible alarm, allowing monitoring of the operational status and alarm condition of the UPS from virtually any
location within the facility, up to 300 feet from the UPS.
Refer to the
Eaton Remote Monitoring Device (RMD) Installation and Operation Manual
, listed in
paragraph
, for additional information.
PredictPulse™ Remote Monitoring and Management Service
– PredictPulse is a subscription monitoring
and management service from Eaton that collects and analyzes data from connected power infrastructure
devices, providing us with the insight needed to make recommendations and take action on your behalf. It’s
also powered by CA Technologies, bringing together the best in hardware and software. Like a second set of
eyes on your power infrastructure, PredictPulse provides 24/7 remote monitoring of alarms and system
performance (load, temperature/humidity, battery health, energy savings and service level) to reduce downtime
risk and expedite repairs. PredictPulse also shares real-time status and trend information via an online
dashboard and smartphone mobile app (Apple and Android), giving subscribers insights about past and current
performance, a list of all active alarms, and asset management data (i.e., battery date codes, last and next
scheduled service dates, firmware versions). The service notifies customers of critical alarms, supports remote
diagnostics, and facilitates smart dispatch of technicians. PredictPulse requires a Power Xpert
®