6
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Minislot (PXGMS) connectivity card in an Minislot communication bay and an Environmental Monitoring Probe
(EMP) for battery temperature/humidity monitoring. See
, for additional information.
11..22..77
A
Addddiittiioonnaall O
Ouuttppuutt S
Suurrggee P
Prrootteeccttiioonn
The Eaton 93PM-L UPS complies with ANSI 62.41 for line surges. However, if added security is required an
additional Surge Protection Device (SPD) can be installed. For this application, a 208V Delta Style SPD Type 1 or
Type 2 installed on the load side is recommended. The SPD must meet the Maximum Continuous Operating
Voltage (MCOV) for a 208V Delta Style SPD. Eaton offers a variety of SPD solutions including the Eaton SPD
Series with various kA ratings options.
11..33
B
Baatttteerryy S
Syysstteem
m
The battery system provides emergency short-term backup power to safeguard operation during brownouts,
blackouts, and other power interruptions.
11..33..11
B
Baatttteerryy C
Coonnffiigguurraattiioonnss
The 93PM-L (60 kW) UPS battery system can be internal to the UPS cabinet, an external Integrated Battery
Cabinet/s (IBC), or a combination of both. The external IBCs are connected in parallel with the internal batteries
to provide extended run time. The battery system is equipped with sealed lead-acid, maintenance-free
batteries.
An external battery disconnect switch or tie point must be used when battery systems are located separate
from the UPS cabinet and wiring exceeds the number of battery terminals available.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
11..33..22
O
Oppttiioonnaall TThheerrm
maall S
Seennssoorr
Thermal runaway protection for VRLA batteries can be provided by adding an optional thermal sensor to the
internal battery section or external battery cabinet.
The sensor is wired to the thermal sensor terminal and programmed to turn the charger off when a trip signal is
received.
The thermal sensor will maintain the trip state until it is reset by service. Service should be called to inspect the
batteries and reset the sensor in case of such an event.
11..44
B
Baassiicc S
Syysstteem
m C
Coonnffiigguurraattiioonnss
The following basic UPS system configurations are possible:
•
Single UPS (20–60 kW) with one to four external battery cabinets
•
Single UPS (20–60 kW) with one to four external battery cabinets and accessory cabinets
•
Multiple UPSs (20–60 kW to a maximum combined rating of 400 kW) with one to four standard external
battery cabinets for each UPS
•
Multiple UPSs (20–60 kW to a maximum combined rating of 400 kW) with one to four standard external
battery cabinets for each UPS and accessory cabinets
The UPS system configuration can be enhanced by adding optional accessories such as a Remote Emergency
Power-off (REPO) control or Minislot communication cards.
Summary of Contents for 93PM-L Series
Page 4: ......
Page 164: ...P 16400071103 P 164000711 03...