Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
47
Table 16. Power Cable Conduit Recommendations (Continued)
UPS Model
UPS
Rating
Voltage
Terminal
Number
of Wires
in Conduit
Minimum
Conduit
Trade Size
(inches)
Number
of
Conduits
93PM-L 60-3
50 kW
208 or 220
Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2
1
208 Vac
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
5
3
1
220 Vac
2-1/2
208 Vac
AC Output
(A, B, C, Neutral, Ground)
5
2-1/2
1
220 Vac
2
DC
Battery
(Positive, Negative, Ground)
3
1-1/4
1
93PM-L 60-3
60 kW
208 or 220
Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
2-1/2
1
AC Input to UPS Bypass
(A, B, C, Neutral, Ground
5
3
2
AC Output
(A, B, C, Neutral, Ground)
5
2-1/2
1
DC
Battery
(Positive, Negative, Ground)
3
1-1/4
1
NOTE
Wires per conduit include neutral and ground wire.
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to
through for wiring recommendations. If an output lockable disconnect is required, it is to be
supplied by the customer.
lists the recommended rating for input and bypass circuit breakers.