86
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
44..66..55
B
Byyppaassss S
Shhuunntt TTrriipp C
Coonnnneeccttiioonnss
NOTE 1
If installing interface wiring connections between standalone cabinets, conduit must be
installed between cabinets.
NOTE 2
Disconnect terminal block plugs from terminal blocks to wire plugs.
To install wiring:
1.
Verify the UPS system is turned off and all power sources are removed. See
Chapter 6
UPS Operating
Instructions
, for shutdown instructions.
2.
If not already opened, open the front door by lifting the latch from the bottom and turning to the right
(counterclockwise) and swing the door open.
3.
If not already removed, remove the screws securing the bottom internal safety shield panel and remove
the panel. Retain the hardware for later use.
4.
If wiring the bypass shunt trip connections using bottom entry access, proceed to
; if wiring the
bypass shunt trip connections using top entry access, proceed to
.
5.
Bottom Entry Wiring.
Route the bypass shunt trip wiring through the bottom of the UPS to the UPS
bypass shunt trip terminals. See
, or
for UPS wiring access information, and
and
for UPS terminal locations.
6.
Proceed to
Step 8
.
7.
Top Entry Wiring.
Route the bypass shunt trip wiring through the top of the UPS and the bottom UPS
inter-cabinet wiring access pass-through to the UPS bypass shunt trip terminals.
8.
Connect the wiring to the bypass shunt trip terminals. See paragraph
UPS System Interface Wiring Preparation
and
for wiring and termination requirements, and
for terminal assignments.
9.
If wiring additional interface or control wiring options, see
for next option to install; otherwise,
proceed to
Step 10
.
10. If removed, reinstall all safety shield panels previously removed and secure with the retained hardware.
11. If removed, reinstall the sidecar front panel and secure with the retained hardware.
12. Close the UPS outside door and secure the latch.
44..66..66
G
Geenneerraattoorr IInntteerrffaaccee C
Coonnnneeccttiioonnss
If ESS is enabled and the UPS will be fed by a site generator at any time, the On Generator building alarm must
be wired and configured to a Building Alarm Input. Wiring the On Generator sensing circuit to a building alarm
allows the UPS to optimize its operation with the generator by transferring the UPS from ESS mode to Normal
(double conversion) mode.
NOTE 1
A UPS building alarm input is used to indicate On Generator.
NOTE 2
Any pair of unused building alarm terminals may be used for On Generator connections.
NOTE 3
Program the building alarm to read On Generator and for either Normally Open (default)
or Normally Closed as required by the generator sensing output.
NOTE 4
If installing interface wiring connections between standalone cabinets, conduit must be
installed between cabinets.
NOTE 5
Disconnect terminal block plugs from terminal blocks to wire plugs.
To Install wiring: