60
Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
44..33
IInntteeggrraatteedd B
Baatttteerryy C
Caabbiinneett IInnssttaallllaattiioonn
If installing Integrated Battery Cabinets (IBCs), refer to the
Eaton 93PM Universal Integrated Battery Cabinet
Installation Manual-Large and Large High Rate
, or the
Eaton 93PM Integrated Battery Cabinet-Small Welded
IBC-SW (432V and 480V) Installation Manual
, listed in paragraph
, for installation
instructions.
!
IMPORTANT
If the Eaton 93PM-L UPS has a SIAC-B, the Integrated Battery Cabinet must be installed on the opposite side of
the UPS away from the SIAC-B.
After the IBC is installed, proceed to paragraph
External AC Power Wiring Installation
to complete the
wiring of the UPS.
44..44
EExxtteerrnnaall A
AC
C P
Poow
weerr W
Wiirriinngg IInnssttaallllaattiioonn
1.
Open the UPS front door by lifting the latch from the bottom and turning to the right (counterclockwise)
and swing the door open.
2.
Remove the screws securing the bottom internal safety shield panel and remove the panel to gain access
to the input, output, and battery power wiring terminals. Retain the hardware for later use.
3.
If the UPS has a Sidecar, loosen the bottom screws and completely remove the top screws securing the
sidecar front panel. Lift the panel upwards and remove from the unit. Retain the hardware for later use.
4.
Remove the screws securing the sidecar internal safety shield panel and remove the panel to gain access
to the interior of the sidecar and the UPS inter-cabinet wiring access pass-through. Retain the hardware for
later use.
5.
If wiring via bottom entry, remove the bottom conduit plate, or plates if sidecar is installed. If wiring via top
entry, remove the top entry conduit plate from the sidecar. For details on conduit plate locations see
,
or
.
NOTE
Top Entry Wiring for the Eaton 93PM-L is only available when the system is ordered
with a sidecar.
6.
Identify all conduit recommendations and mark their location.
7.
Proceed to the appropriate wiring configuration:
•
Standalone UPS or UPS with Top Entry Sidecar (No Breakers)
, go to Section
Standalone UPS or UPS with Top Entry Sidecar (No Breakers).
.
•
UPS with 2-Breaker Sidecar (MBP and MIS)
, go to Section
UPS with 2-Breaker Sidecar (MBP and MIS)
.
•
UPS with 3-Breaker Sidecar (BIB, MBP and MIS)
, go to Section
UPS with 3-Breaker Sidecar (BIB, MBP and MIS)
.
•
UPS with 4-Breaker Sidecar (RIB, BIB, MBP and MIS)
, go to Section
UPS with 4 -Breaker Sidecar (RIB, BIB, MBP and MIS)
.
Summary of Contents for 93PM-L Series