Eaton 93PM-L 20 – 60 kW (208V) UPS Installation and Operation Manual P-164000711—Rev 03
Figure 38. Building Alarm Terminal Block Connector Assignments
Building Alarm 5 Return
Building Alarm 5
Building Alarm 4 Return
Building Alarm 4
Building Alarm 1
Building Alarm 1 Return
Building Alarm 2
Building Alarm 2 Return
Building Alarm 3
Building Alarm 3 Return
UPS Building Alarms
1 2 3 4 5 6 7 8 9 10
Table 22. Relay Contact Connections and Wire Terminations
Termi-
nal
Name
Description
Recommended
Minimum
Wire Size
Size of Pressure
Termination
Tightening
Torque
1
Relay Contact NC
Output: General purpose
normally-closed (NC) relay
contact
Twisted Pair
Wires #18 AWG
#14 #30 AWG
2 lb in
(0.22-0.25 Nm)
3
Relay Contact
Common
2
Relay Contact NO
Output: General purpose
normally-open (NO) relay
contact
3
Relay Contact
Common
Figure 39. Relay Contact Terminal Block Connector Assignments
UPS Relay Output
1 2 3
NO_Out
NC_Out
Com