Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
97
77..22..88
S
Syysstteem
m C
Coonnttrroollss
Tap the
CONTROLS
tab on the main menu navigation bar to display the Controls screen. Double conversion
operation, transfer to bypass, shutdown, and charger control commands are controlled through this screen. In
addition, the screen displays the current status of the UPS.
describes the control functions and provides instructions to access and use the command menu
screens.
lists the typical System Status Screen Messages that are displayed during UPS operation.
For UPS operating instructions using the System Controls, see paragraph
or
Multiple External Parallel System Operation
through
show the major control screens.
Table 23. Controls Menu Operation
Function
Subfunction
Operation
System
Controls
The
CONTROLS
tab on the main menu navigation bar displays the
System Controls screen.
System Status
GO ONLINE
starts the UPS in Double Conversion mode or transfers the
UPS to Double Conversion mode from Bypass mode.
Bypass
GO TO BYPASS
starts the UPS in Bypass mode or transfers the UPS
to Bypass mode from Double Conversion mode.
Charger
TURN ON CHARGER/TURN OFF CHARGER
sets the battery charger
on or off.
Battery Test
RUN BATTERY TEST
starts the battery test.
Table 24. Typical System Status Messages
Function
Message
UPS
Double Conversion; Bypass; ESS
Bypass
Off; On; Available
Charger
Charger Resting; Charger
Summary of Contents for 93PM Series
Page 4: ......
Page 138: ...16400022707 164000227 07 ...