Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Battery Voltage
216 cell – 432 Vdc
240 cell – 480 Vdc
Battery Charging Capacity
16.5 A maximum per 50 kW module at full load at nominal input voltage
1100..22..22 U
UP
PS
S O
Ouuttppuutt
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Output Voltage
480 Vac Wye, 3W + ground. No Neutral.
Output Voltage Harmonic Content
1% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See
or
.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase Displacement
< 2.5° for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
1 Hz per second (default setting)
Load Compatibility
0.8 pF Leading
0.8 pF Lagging
Overload Capability
<110% for 10 minutes
<125% for 60 seconds
<150% for 10 seconds
>150% for 300 milliseconds
1100..22..33 U
UP
PS
S EEnnvviirroonnm
meennttaall
Operating Temperature
5 to 40°C (41 to 104°F) without derating. The recommended operating temperature
is 25°C (77°F).
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Storage Temperature
-25 to +55°C, excluding batteries (prolonged storage above 40°C causes rapid
battery self-discharge)
Relative Humidity (operating and
storage)
5 to 95%, noncondensing
Acoustical Noise
100 kW at 100% load – 65 dBA at a 1m distance, per ISO 7779
Agency Markings
UL 924 Auxiliary Lighting and Power Equipment
Safety: UL1778 5th Ed./CSA22.2 No. 107.3-14 3rd Ed.
EMI Emissions and Immunity
Meets IEC 62040-2 C3 and FCC Part 15 Subpart B Class A, ICES-003, CISPR 22
Electrostatic Discharge (ESD)
Immunity
Meets IEC 61000-4-2 Level 3 specifications. Withstands up to 4 kV contact pulse
without damage and with no disturbance or adverse effect to the critical load.