Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
5
bypass to supply the load. The SIAC-B is housed in a cabinet attached to the UPS cabinet. The SIAC-B may be
installed on either the right or left side of the UPS cabinet. The SIAC-B can also be used for top entry wiring
access.
11..22..55
S
Siiddeeccaarr IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--TTiiee
A Sidecar Integrated Accessory Cabinet-Tie (SIAC-T) provides the ability to parallel up to four UPSs together for
increased capacity and/or redundant capability. The SIAC-T is housed in a cabinet attached to the UPS cabinet.
The SIAC-T may be installed on either the right or left side of the UPS cabinet. The SIAC-T can also be used for
top entry wiring access.
11..22..66
S
Siiddeeccaarr IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--TTiiee B
Byyppaassss
A Sidecar Integrated Accessory Cabinet-Tie Bypass (SIAC-TB) provides the ability to parallel two UPSs together
for increased capacity and/or redundant capability. In addition, maintenance bypass functions enable power to
completely bypass the UPS power module. The SIAC-TB is housed in a cabinet attached to the UPS cabinet.
The SIAC-TB may be installed on either the right or left side of the UPS cabinet. The SIAC-TB can also be used
for top entry wiring access.
11..22..77
IInntteeggrraatteedd A
Acccceessssoorryy C
Caabbiinneett--TTiiee
An Integrated Accessory Cabinet-Tie (IAC-T) provides the ability to parallel up to four UPSs together for
increased capacity and/or redundant capability. The IAC-T is housed in a single, free-standing cabinet designed
for line-up-and-match installation, but may be installed separate from the UPS cabinet. The recommended
installation location for an adjacent IAC-D is to the left of the UPS cabinet.
11..22..88
P
Paarraalllleell S
Syysstteem
m
NOTE
All UPSs in a parallel system must have the same battery configuration. Each UPS
requires a separate battery cabinet.
A parallel UPS system with up to eight UPSs can be installed to provide a parallel capacity and/or redundant
system. This load sharing system provides more capacity than a single UPS, and can provide backup,
depending on the load and configuration. In addition, when one UPS is taken out of service for maintenance or
is not operating properly, a redundant UPS continues to supply uninterrupted power to the critical load. A built-
in Controller Area Network (CAN) provides connectivity for system metering and operational mode control. The
parallel system consists of two to four UPSs each with a parallel CAN, and an IAC-T, SIAC-T, or SIAC-TB to act
as a tie point and to control the output.
11..22..99
TToopp EEnnttrryy W
Wiirriinngg S
Siiddeeccaarr
If required, a sidecar is available for top entry power wiring. The sidecar performs the function of a wireway
routing the wires to the terminals mounted at the bottom of the UPS cabinet. The sidecar can be installed on
the left or right side of the UPS cabinet.
11..22..1100 M
Moonniittoorriinngg aanndd C
Coom
mm
muunniiccaattiioonn
Minislot Cards
– Optional Minislot cards support several protocols, such as SNMP, SMTP, HTTP, Modbus
®
,
and TCP/IP. See
, for additional information on monitoring and communication
features.
Remote Monitoring Device (RMD)
– An optional RMD contains a touch screen status display and a local
audible alarm, allowing monitoring of the operational status and alarm condition of the UPS from virtually any
location within the facility, up to 300 feet from the UPS. Refer to the
Eaton Remote Monitoring Device (RMD)
Installation and Operation Manual,
listed in paragraph
, for additional information.