Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
23
Figure 9. UPS Cabinet with Left or Right-Mounted Sidecar Center of Gravity
Dimensions are in millimeters [Inches]
Weight and Center of Gravity with Left-Mounted Sidecar (letters A, B, and C map to
)
A
mm (in)
B
mm (in)
C
mm (in)
Weight
kg (lb)
Eaton 93PM-100-1 UPS with Top Entry Wiring Sidecar
(no breakers)
844 (33.2)
542 (21.3)
409 (16.1)
406 (894)
Eaton 93PM-100-2 UPS with Top Entry Wiring Sidecar
(no breakers)
911 (35.8)
541 (21.3)
419 (16.5)
469 (1034)
Eaton 93PM-100-3 UPS with Top Entry Wiring Sidecar
(no breakers)
1001 (39.4)
541 (21.3)
427 (16.8)
539 (1188)
Eaton 93PM-100-1 UPS with four breaker SIAC-B
855 (33.7)
568 (22.4)
390 (15.4)
433 (954)
Eaton 93PM-100-2 UPS with four breaker SIAC-B
917 (36.1)
564 (22.2)
402 (15.8)
496 (1094)
Eaton 93PM-100-3 UPS with four breaker SIAC-B
1001 (39.4)
561 (22.1)
412 (16.2)
566 (1248)