Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
35
Table 12. Recommended DC Input Battery Disconnect Circuit Breaker Ratings (240 Cell)
Output Rating
UPS Model
UPS Rating
480V
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW
60A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
30 kW
90A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW
125A
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW
150A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW
175A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
200A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW
225A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
250A
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW
300A
33..22..44
U
UP
PS
S S
Syysstteem
m IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
NOTE
Refer to the
Eaton 93PM Sidecar Integrated Accessory Cabinet-Tie and Tie Bypass (50
kW and 100 kW SIAC-T, and 50 kW and 100 kW SIAC-TB) Installation and Operation
Manual,
listed in paragraph
, for SIAC-T and SIAC-TB interface
wiring preparation and requirements.
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.
WARNING
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
should be rated for 600V, 1A minimum. 12 AWG maximum wire size.
•
Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
rated for 24V, 1A minimum.
•
Because of the battery shunt trip wiring route in the UPS cabinet, the wire should be rated for a minimum
of 600V.