Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
123
C
Chhaapptteerr 1100 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
1100..11
M
Mooddeell N
Nuum
mbbeerrss
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Model
Power Rating
Frequency
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
20 kW
50/60 Hz
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
30 kW
50/60 Hz
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
40 kW
50/60 Hz
Eaton 93PM-100-1
Eaton 93PM-100-2 (N+1)
50 kW
50/60 Hz
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
60 kW
50/60 Hz
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
70 kW
50/60 Hz
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
80 kW
50/60 Hz
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
90 kW
50/60 Hz
Eaton 93PM-100-2
Eaton 93PM-100-3 (N+1)
100 kW
50/60 Hz
1100..22
S
Sppeecciiffiiccaattiioonnss
The following sections detail the input, output, environmental, and battery specifications for the UPS.
1100..22..11 U
UP
PS
S IInnppuutt
Operating Input Voltage
480 Vac Wye, 3W + ground. Neutral not used.
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
or
Reduced for Generator
Adjustable
Input Current Harmonic Content
3% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801 4
Summary of Contents for 93PM Series
Page 4: ......
Page 138: ...16400022707 164000227 07 ...