28
Eaton 93PM UPS 480V Three-Wire – 100 kW Frame Installation and Operation Manual 164000227—Rev 07
Table 4. Input/Output Ratings and External Wiring Recommendations: Eaton 93PM-100-1 and 93PM-100-2 (N+1)
(Continued)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
10
(1)
10
(1)
10
(1)
8
(1)
NOTE
Callout letters
A
,
B
,
C
and
D
map to
through
NOTE
Line-up-and-match battery wiring with a 105°C rating is factory supplied with the Eaton 93PM Integrated Battery Cabinet
(IBC).
Table 5. Input/Output Ratings and External Wiring Recommendations: Eaton 93PM-100-2 and 93PM-100-3 (N+1)
Basic Unit Rating
Units
Rating 50/60 Hz
kW
60
70
80
90
100
Input and Output Voltage
Volts
480/
480
480/
480
480/
480
480/
480
480/
480
AC Input to UPS Rectifier (0.99 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
94
108
120
133
146
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
1
(1)
1/0
(1)
2/0
(1)
2/0
(1)
3/0
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
6
(1)
6
(1)
6
(1)
6
(1)
6
(1)
AC Input to UPS Bypass (Three Wire, Dual-
Feed)
Full Load Current
(3) Phases, (1) Ground
B
Amps
94
108
120
133
146
Minimum Conductor Size (Phase A, B, and C)
Number per Phase
AWG or kcmil
(each)
1
(1)
1/0
(1)
2/0
(1)
2/0
(1)
3/0
(1)
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
6
(1)
6
(1)
6
(1)
6
(1)
6
(1)
DC Input from External Battery (Line-Up-and-
Match Eaton 93PM IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps (216
cell)
Total Amps (240
cell)
149
134
165
156
198
178
223
200
247
223
Minimum Conductor Size (Phase Pos. and Neg.)
Number per Pole
AWG or kcmil
(each)
2/0
(1)
See
Note
2/0
(1)
See
Note
2/0
(1)
See
Note
2/0
(1)
See
Note
2/0
(1)
See
Note
Minimum Conductor Size (Ground)
Number
–
AWG or kcmil
(each)
4
(1)
4
(1)
4
(1)
4
(1)
4
(1)
DC Input from External Battery (Standalone
Eaton 93PM IBC)
(1) Positive, (1) Negative, (1) Ground
C
Total Amps (216
cell)
Total Amps (240
cell)
149
134
165
156
198
178
223
200
247
223