Eaton 93PM 50-100 kW SIAC-T and 50-100 kW SIAC-TB Installation and Operation Manual P-164000370—Rev 04
15
Weight and Center of Gravity with Left-Mounted 50 kW SIAC-TB (letters A, B, and C map to
)
Internal
Battery
Strings
Frame
A
mm (in)
B
mm (in)
C
mm (in)
Installed
Weight
kg (lb)
Eaton 93PM-50-1 UPS
0
Capacity
981 (38.6)
588 (23.1)
386 (15.2)
414 (913)
3
Capacity
839 (33.0)
559 (22.0)
431 (17.0)
774 (1706)
4
Capacity
857 (33.7)
555 (21.9)
437 (17.2)
879 (1937))
5
Capacity
888 (35.0)
551 (21.7)
442 (17.4)
983 (2168)
0
Redundant
927 (36.5)
588 (23.1)
389 (15.3)
430 (948)
3
Redundant
805 (31.7)
560 (22.0)
430 (16.9)
767 (1691)
Eaton 93PM-50-2 UPS
0
Redundant
1020 (40.2)
581 (22.9)
401 (15.8)
494 (1088)
3
Redundant
870 (34.3)
559 (22.0)
434 (17.1)
831 (1831)
Weight and Center of Gravity with Right-Mounted 50 kW SIAC-TB (letters A, B, and C map to
Internal
Battery
Strings
Frame
A
mm (in)
B
mm (in)
C
mm (in)
Installed
Weight
kg (lb)
Eaton 93PM-50-1 UPS
0
Capacity
1007 (39.6)
561 (22.1)
370 (14.6)
414 (913)
3
Capacity
830 (32.7)
542 (21.3)
328 (12.9)
774 (1706)
4
Capacity
851 (33.5)
539 (21.2)
323 (12.7)
879 (1937)
5
Capacity
887 (34.9)
538 (21.2)
318 (12.5)
983 (2168)
0
Redundant
997 (39.3)
562 (22.1)
367 (14.4)
430 (948)
3
Redundant
821 (32.3)
544 (21.4)
329 (13.0)
767 (1691)
Eaton 93PM-50-2 UPS
0
Redundant
1052 (41.4)
558 (22.0)
356 (14.0)
494 (1088)
3
Redundant
866 (34.1)
543 (21.4)
325 (12.8)
831 (1831)
Summary of Contents for 93PM SIAC-T