UPS System Installation
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
4-15
Figure 4-12. Wire Tie Anchors
Figure 4-13. Building Alarm Terminal Block Connector Assignments
Wire Tie Anchors
Table 4-1. Building Alarm Connections and Wire Terminations
Terminal Name
Description
Recommended
Wire Size
Size of Pressure
Termination
Tightening Torque
10
Building Alarm 1
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Twisted Pair Wires
#18 AWG
#14
30 AWG
2 lb in
(0.22-0.25 Nm)
9
Building Alarm 1 Return
8
Building Alarm 2
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Twisted Pair Wires
#18 AWG
#14
30 AWG
2 lb in
(0.22-0.25 Nm)
7
Building Alarm 2 Return
6
Building Alarm 3
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Twisted Pair Wires
#18 AWG
#14
30 AWG
2 lb in
(0.22-0.25 Nm)
5
Building Alarm 3 Return
4
Building Alarm 4
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Twisted Pair Wires
#18 AWG
#14
30 AWG
2 lb in
(0.22-0.25 Nm)
3
Building Alarm 4 Return
2
Building Alarm 5
Input: Programmable UPS alarm, activated by a
remote dry contact closure
Twisted Pair Wires
#18 AWG
#14
30 AWG
2 lb in
(0.22-0.25 Nm)
1
Building Alarm 5 Return
UPS Building Alarms
1
2
3
4
5
6
7
8
9 10
Building Alarm 5
Building Alarm 5 Return
Building Alarm 4
Building Alarm 4 Return
Building Alarm 1 Return
Building Alarm 1
Building Alarm 2 Return
Building Alarm 2
Building Alarm 3 Return
Building Alarm 3
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...