UPS System Installation
Eaton 93PM UPS (20–50 kW, 480V Four Wire – 50 kW Frame) Installation and Operation Manual P-164000540—Rev 4
www.eaton.com/powerquality
4-19
Figure 4-16. Battery Detect and Shunt Trip Terminal Assignments
Figure 4-17. Battery Configuration Jumper Assignments
4.7.3
Installing Thermal Sensor Interface Connections
Battery Detect Internal
Battery Detect Return
Ground
Battery
S
hunt Detect
Battery
S
hunt Trip
V
CC
Not Used
Not Used
Ground
MB
S
Detect
Battery Detect
and
S
hunt Trip
TB10
10
9
8
7
6
5
4
3
2
1
Table 4-3. External Battery Detect and Shunt Trip Connections and Wire Terminations
Terminal Name
Description
Recommended
Minimum Wire Size
Size of Pressure
Termination
Tightening Torque
5
VCC
Output: Signal used to open battery breaker
or disconnect
Twisted Pair Wires
#18 AWG Use wire
rated for 600V and
Class 1 wiring
methods.
#12-#22 AWG
5–7 lb in
(0.56–0.79 Nm)
6
Battery Shunt Trip
7
Battery Shunt Detect
Input: Signal used to indicate an open battery
breaker. Also used to select battery configuration.
8
Ground
10
9
8
7
6
5
4
3
2
1
UP
S
Battery
Detect and
S
hunt Trip
TB10
Jumper
Internal
Batteries
10
9
8
7
6
5
4
3
2
1
UP
S
Battery
Detect and
S
hunt Trip
TB10
Jumper
Internal and
External
Batteries
10
9
8
7
6
5
4
3
2
1
UP
S
Battery
Detect and
S
hunt Trip
TB10
Jumper
External
Batteries
Jumper
Summary of Contents for 93PM UPS
Page 1: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 2: ......
Page 3: ...Eaton 93PM UPS 20 50 kW 480V Four Wire 50 kW Frame Installation and Operation Manual...
Page 25: ...Section 1 Installation...
Page 26: ......
Page 87: ...Section 2 Operation...
Page 88: ......
Page 145: ......
Page 146: ...P 164000540 4 P 164000540 4...