25-75 kW
User's and Installation Guide
28
• Specification is for copper wire with a 90 °C rating.
• The bypass feed into this equipment uses four wires. The rectifier feed into this equipment uses three or
four wires. The phases must be symmetrical about ground (from a Wye source) for proper equipment
operation.
• If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a
neutral and there is no neutral conductor connected at the bypass input, a neutral must be installed to source
star point.
• A readily accessible disconnect device must be incorporated in all fixed input wiring.
Table 3-5: Maximum Support Multi-core Cable Sizes
UPS
rating
Rectifier
input
(L1, L2, L3)
Bypass
input
(L1, L2, L3)
UPS
output
(380/400/415V)
(L1, L2, L3)
N
PE
Battery
(BAT+, BAT-)
75 kW
70*1 mm
2
70*1 mm
2
70*1 mm
2
70*2 mm
2
70*1 mm
2
70*2 mm
2
Table 3-6: Minimum Recommended Multi-core Cable and Fuse Sizes
UPS
rating
Rectifier
input
(L1, L2, L3)
Bypass
input
(L1, L2, L3)
UPS
output
(380/400/415V)
(L1,L2,L3)
N
PE
Battery
(BAT+, BAT-)
Fuse
Cable
Fuse
Cable
Cable
Cable
Cable
Fuse
Cable
75 kW
160A
35*1 mm²
180A 35*1 mm²
35*1 mm²
50*1 mm² 50*1 mm²
210A 50*1 mm²
NOTE
Bypass fuse type should be greater than 10 times rated 12
t
20ms.
Table 3-7: Rated and Maximum Currents for Rated Power and Voltage
Rated
power
Rated
voltage
Rectifier
input
Rated current
Rectifier
input
Max.current
UPS
Output/
Bypass
Rated current
UPS
Output/
Bypass
Max.current
Battery
Rated current
Battery
Max.current
25 kW
380
38
45
38
42
52
63
400
36
42
36
40
52
63
415
35
41
35
39
52
63
50 kW
380
76
89
76
84
104
125
400
72
85
72
80
104
125
415
70
82
70
78
104
125
75 kW
380
114
134
114
127
156
188
400
108
127
108
120
156
188
415
104
122
104
116
156
188
Summary of Contents for 93PR 25(75)
Page 1: ...User s and Installation Guide Eaton 93PR UPS 25 75 kW ...
Page 2: ......
Page 3: ...Eaton 93PR UPS 25 75 kW User s and Installation Guide ...
Page 96: ......
Page 97: ......
Page 98: ...614 02087 00 ...