25-75 kW
User's and Installation Guide
80
8.2 UPS System Input
Table 8-2: UPS System Input
Rated Input Voltage
Voltage Tolerance, (Rectifier Input)
Voltage Tolerance, (Bypass Input)
220/380 V; 230/400 V; 240/415 V
Rated input voltage -15 % / +20 %
Rated input voltage -10 % / +10 %
Rated Input Frequency
50 or 60 Hz, user configurable
Frequency Tolerance
40 to 72 Hz
Number of Input Phases, (Rectifier Input)
Number of Input Phases, (Bypass Input)
3 N
Input Power Factor
0,99
Rated Mains Input Current
Maximum Mains Input Current
See Table 3-7: Rated and maximum currents for rated
power and voltage on page 31
Input Current Distortion at Rated Input Current,
iTHd
< 3 %
Rectifier Ramp-up, Rectifier Start and Load Step
5 A/s per UPM (default), configurable. Min 1A/s per
UPM
Backfeed Protection
Yes, for rectifier and bypass lines