25-75 kW
User's and Installation Guide
82
8.4 Battery Specification
Table 8-4: Battery Specification
Battery Type
VRLA, 12 Vdc
Battery Quantity
40-42 blocks, 240-252 cells per battery string, default
40 blocks per battery string.
Note! Battery strings with different battery quantity
and voltage may not be connected in parallel!
Battery Voltage
480 V (40 blocks) to 504V (42 blocks)
Recharge Profile
ABM or float charge
End of discharge Voltage
1.67 VPC to 1.75 VPC, configurable or automatic (load
adaptive)
Charge Current
Configurable:
Single UPM default 4A, configurable, max 25A per
UPM
Battery Start Option
Yes
Note! For external battery connection, 24 VDC Shunt Trip signal wiring from the UPS must be connected to
the auxiliary signal connection of the battery breaker.