Chapter 7 UPS MAINTENANCE
The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies
are located for easy removal, with very little disassembly. This design allows authorized service personnel to
perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your
UPS system to keep it running properly. Regular routine checks of operation and system parameters enable your
system to function efficiently for many trouble-free years.
7.1. Important Safety Instructions
Remember that your UPS system is designed to supply power
EVEN WHEN DISCONNECTED FROM
THE UTILITY POWER
. The UPS module interiors are unsafe until the DC power source is disconnected
and the electrolytic capacitors are discharged. After disconnecting the utility power and the DC power,
authorized
service personnel should wait at least five minutes for capacitor bleed-off before attempting internal access
to the UPS module.
NOTE
•
Servicing and maintenance should be performed by qualified service personnel only.
• LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open
or protective panels removed. Do not make any assumptions about the electrical state of any
cabinet in the UPS system.
Since each battery string is an energy source in itself, opening the battery circuit breaker does not
deenergize the voltage within the battery string.
DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA
OF THE
BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRING
.
If you suspect that a battery string needs service, you should contact your service representative.
If the string requires service, refer to the battery manufacturer’s operating manual for instructions on
battery maintenance or contact your service representative.
Observe these precautions when working on or around batteries:
•
Remove watches, rings, or other metal objects.
•
Use tools with insulated handles.
•
Wear rubber gloves and boots.
•
Do not lay tools or metal parts on top of batteries or battery cabinets.
•
Disconnect the charging source prior to connecting or disconnecting terminals.
•
Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact
with any part of a grounded battery can result in electrical shock. The likelihood of such shock is
reduced if such grounds are removed during installation and maintenance.
•
When replacing batteries, use the same number of sealed, lead-acid batteries.
•
Proper disposal of batteries is required. Refer to your local codes for disposal requirements.