Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
123
Copyright © 2021 Eaton Corporation plc. All rights reserved.
8.3. UPS System Output
Table 8-3: UPS System Output
Number of Output Phases
3 N (Optional)
Rated Output Voltage
220/380 V; 230/400 V; 240/415 V, configurable
Total Voltage Harmonic Distortion
100% Linear Load < 1%
100% Non-Linear Load < 5%
Rated Output Frequency
Output Frequency Variation
Slew Rate
50 or 60 Hz, configurable
± 0,1 Hz
1 Hz/s
Overload Capability at Ambien 30°C
(Ambient Temperature)
10 min 125% load
Overload Capability at Ambient 30°C
(Double Conversion Mode)
60 min 102-110 % load
10 min 111-125 %
30 sec 126-150 % load
300 ms > 150 % load
Overload Capability at Ambient 30°C
(on Inverter, Stored Energy Mode)
1 min 102-110 % load
300 ms > 110 % load
Overload Capability at Ambient 30°C
(on Bypass)
Continuous < 115% load,
10 ms 1000% load
Note! Bypass fuses may limit the overload capability.
Output Current
See
Rated and Maximum Currents for Rated
Load Power Factor, (Rated)
1.0
Load Power Factor, (Permitted Range)
From 0.8 lagging to 0.8 leading