8.5.
UPS Environmental Specifications
Table 8-5:
UPS Environmental Specifications
Ambient Service Temperature Range, (UPS)
+0°C to +30°C*, No output power derating required.
Ambient UPS Storage Temperature Range
From -25°C to +55°C in the protective package*
Maximum Service Altitude
Maximum 2000m (6600ft) with 1% derating per each
additional 100m.
Relative Humidity Range
5 to 95%, no condensation allowed
Acoustic Noise at 1 m
At 1m per ISO 7779 standard
300kW :
≦
74.6dB
600kW :
≦
78.8dB
1200kW :
≦
81.8 dB
EMC
IEC 62040-2 C3
*Maximum recommended operating and storage temperature with VRLA batteries is +25°C.
Storage condition for UPS and spare parts store one year (refer unit SN).
Place
Indoor
Dusty
Well
Storage Temperature
<40°C
Storage Humidity
< 70% RH
Other
With original package
Please re –evaluate the storage time if can not meet above storage condition.