2.7.
Basic System Configurations
UPS Power Rating
The power rating of a single UPS is determined by the number of UPM, but the maximum power could not
exceed the static bypass rating.
The UPS frames can be connected in parallel to create even larger systems. A maximum of four
300kW/600kW UPS frames can be connected in parallel and a maximum of two 1200kW UPS frame
can be connected in parallel. Above four UPS in parallel requirement can ask help from Eaton technical
solution team to customization design.
UPS Internal Options
The following table shows different standard and optional UPS options and the models where they apply.
Table 2-1: Standard and Optional UPS Options
300 kW
600 kW
1200 kW
Smart touch screen display for system
control and monitoring*
Standard
Standard
Standard
SNMP web interface (See
Section
)
Option
Option
Option
Internal MBS*
Standard (Internal)
Standard (Internal)
/
Rectifier input switch*
Option
Option
/
UPS output switch*
/
Bypass switch*
/
Integrated backfeed protection(K5)*
Standard
Standard
Standard
Top Exhaust Accessory*
Option
Option
Option
Single Input
Option
Option
Option
Dual Input
Standard
Standard
Standard
3-Wire/4-Wire*
Option
Option
Option
Air filter
Standard
Standard
Standard
*:
Need to be assembled in the factory.
Additional options and accessories are also available. These include different software and connectivity
options and external switchgear and power distribution options.