Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
41
Copyright © 2021 Eaton Corporation plc. All rights reserved.
3.3.2. UPS System Interface Wiring Preparation
Control wiring for features and options should be connected at the customer interface terminal
blocks located on top front of the UPS, behind the door.
DANGER
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation
to the mains is required.
Read and understand the following notes while planning and performing the installation:
•
All interface wiring is to be provided by the customer.
•
When installing internal interface wiring to Mini-slot terminals, route the wiring through the
internal opening in the Mini-slot communication bay.
•
All signal inputs or remote features require an isolated normally-open contact or switch (rated
at 24 Vdc, 20 mA minimum) connected between the alarm input and common terminal. All
control wiring and relay and switch contacts are customer-supplied. Use twisted-pair wires for
each alarm input and common.
•
The signal inputs can be programmed to display the alarm functional name.
•
LAN and telephone drops for use with Mini-slot cards must be provided by facility planners or
the customer.
•
The UPS Battery Aux and 48 Vdc Shunt release signal wiring from the UPS to the DC source
disconnect device is optional.
•
Battery Aux and 48 Vdc Shunt release wiring should be a minimum of 1.5 mm².
•
The Remote EPO feature opens all switchgear in the UPS cabinet and isolates power from
your critical load. Local electrical codes may also require tripping upstream protective devices
to the UPS.
•
The Remote EPO switch must be a dedicated switch not tied to any other circuits.
•
A jumper wire must be connected between pins 1 and 2 on connector EPO, if the
normallyclosed (NC) remote EPO contact is used.
•
Remote EPO wiring should be a minimum of 0.75 mm² and a maximum of 2.5 mm².
•
The maximum distance between the Remote EPO and the UPS cannot exceed 150 meters.
•
Alarm relay contacts have a maximum current rating of 5 A and a switched voltage rating of
30 Vac (RMS) and 30 Vdc.
•
Alarm relay wiring should be a minimum of 0.75 mm².
Summary of Contents for 93PR Series
Page 1: ...60 1200 kW Installation and Operation Manual Eaton 93PR UPS ...
Page 2: ......
Page 142: ......
Page 143: ...614 40061 01 ...