Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
69
Copyright © 2021 Eaton Corporation plc. All rights reserved.
Table 4-5: Normally-Closed REPO Connections and Wire Terminations
From REPO
Station
Switch
Contact
Block
(Either Block)
UPS
REPO
Terminal
Name
Description
Recommended
Minimum Wire
Size
Size of Wire
Termination
Tightening
Torque
1 NC
1
EPO_ A_B
Input: Normally-closed
dry contact used to
activate UPS
EPO from a remote
switch
Twisted Pair
Wires #18 AWG #16-#30 AWG
2 lb in
(0.22-0.25 Nm)
2 NC
2
GNDISO
Figure 4-19: Normally-Closed REPO Switch Wiring
NOTE
The REPO switch must be a latching-type switch not tied to any other circuits.