Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
5
Copyright © 2021 Eaton Corporation plc. All rights reserved.
1.4. Environment
The UPS must be installed according to the recommendations in this manual. Under no circumstances
should the UPS be installed in an airtight room, in the presence of flammable gases, or in an environment
exceeding the specifications.
Excessive amount of dust in the operating environment of the UPS may cause damage or lead to
malfunction. The UPS should always be protected from the outside weather and sunshine. In order to
maximize internal battery service life time, the recommended operating temperature range is from +20 to
+25 ºC.
WARNING
Hydrogen and oxygen gases are emitted from batteries into the surrounding atmosphere during
charge, float charge, heavy discharge, and overcharge. Explosive gas mixture may be created if
the hydrogen concentration exceeds 4% by volume in air. Necessary air flow rate for ventilation of
UPS location must be ensured.
1.5. For More Information
Address any inquiries about the UPS and battery cabinet to the local office or agent authorized by the
manufacturer. Please quote the type code and the serial number of the equipment. Call your local service
representative if help is needed with any of the following:
• Scheduling initial startup
•
User’s and Installation Guide
•
Regional locations and telephone numbers
•
A question about any of the information in this manual
•
A question this manual does not answer