Eaton 93PR 60-1200 kW UPS
Installation and Operation Manual
27
Copyright © 2021 Eaton Corporation plc. All rights reserved.
The UPS cabinets use forced air cooling to regulate internal component temperature. You must
allow clearance in front of and behind each cabinet for proper air circulation.
The clearances required around the UPS cabinet in both of these situations are shown in
Table 3-2: UPS Cabinet Minimum Clearances
Rear Exhaust Clearance
Top Exhaust Clearance
From Top of Cabinet
D1
300 mm
800 mm
From Front of Cabinet
D2
1000 mm
1000 mm
From Back of Cabinet
D3
800 mm
*
600 mm
**
* Cabling may require more space.
** Service space (when the two sides are not against other cabinets, the 300kW top air configuration UPS can be
installed against the wall).
The picture takes a 600kW cabinet as an example
D1
D1
D2
D2
D3
D3
Figure 3-1: UPS Cabinet Clearances. See
.