Number of input phases (rectifier & bypass) 3 phases, N
Input power factor
0.99
Rated mains input current
Maximum mains input current
See Table
10
Input current distortion at rated input cur-
rent, iTHD
8 kW, 10 kW: resistive load <3%, non-line-
ar load <5%
15–40 kW: resistive load <3%, non-linear
load <4%
Rectifier ramp-up, rectifier start and load
step
10 A/s (default), configurable.
Min 1A/s
Backfeed protection
Yes, for rectifier and bypass lines
9.3 UPS system output
Number of output phases
3 phases, N
Rated output voltage
220/380 V; 230/400 V; 240/415 V, configu-
rable
Rated output frequency
50 or 60 Hz, user configurable
Total voltage harmonic distortion:
100 % linear load
100 % non-linear load
< 1.5%
< 3.5%
Output frequency variation
+/- 0.1 Hz (with 1 UPM), +/- 0.15 Hz (with 2
UPMs)
Slew rate
1 Hz/s
Output current
See Table
10
Overload capability at ambient 40 °C (in
the double conversion mode)
102 – 110 % rated power for 10 min
111 – 125 % rated power for 60 s
126 – 150 % rated power for 10 s
> 150% rated power for 300 ms
Overload capability at ambient 40 °C (in
the stored energy mode)
102 – 110 % rated power for 10 min
111 – 125 % rated power for 60 s
126 – 150 % rated power for 10 s
> 150% rated power for 300 ms
Overload capability at ambient 40 °C (in
the bypass mode)
Continuous ≤ 125% load
Transient ≤ 1000% RMS current for 20 ms
Note! Bypass fuses may limit the overload
capability