18
5. Short-circuit the input terminals (1, 2 and 3) with the jumper provided in
the accessories kit. Connect the wires to the respective terminals,
following exactly the instructions below:
Input line
a - Ensure that the upstream magneto-thermal switch is open.
b - Connect the earth wire to screw A.
c - Connect the neutral wire to terminal 4.
d - Connect the live wire to terminal 1.
Output line
a - Connect the earth wire to screw B.
b - Connect the neutral wire to terminal 5.
c - Connect the live wire to terminal 6.
R.E.P.O.
a - The REPO connection (between terminal 5 and 6) is normally open.
For more information please refer to the REPO section of this
manual
Fig.3-5 10~20K single phase input terminal view
6. Tighten the terminals well, close the backpanel cover and secure it with
the screws taken out earlier.
For 10 to 15kVA the suggested tighten force is 1.2~1.6Nm. For 20kVA,
the suggested tighten force is 2.5~3 Nm.
JUMPER