36
Bypass line not available:
locks after 10 s
Overload load > 150%
Bypass line available:
activates the bypass
after 100 ms, then
locks after 1 s
Bypass line not available:
locks after 1 s
OTHER
Leakage current to
earth
[mA]
< 8mA
Ambient temperature
[°C]
0
– 40
Humidity
< 95% without condensation
Protection devices
Batteries deep discharge - overcurrent - short circuit -
overvoltage - undervoltage - circuit breaker
Dimensions
W x D x H
[mm]
262 x 613x 709
350 x 706 x 818
Weight
[kg]
68.8
86
(29 XL)
147
160
(48.5 XL)
Operating Temperature
0
o
C to 40
o
C
Operating humidity
0-95% no condensing
Altitude
Up to 1,000 meters above sea level with 10% derating per
1000m
Storage temperature
-15
o
C to 60
o
C without batteries
0~35°C with batteries
EBM
180VDC 9Ah
240VDC 9Ah
Nominal battery voltage
[Vdc]
180Vdc
240Vdc
Dimensions W x D x H
[mm]
262 x 580 x 709
Weight
[kg]
105.5
132.4