Page 15
3.3.3
EBM
W
IRING
C
ONNECTION
It is possible to connect more than one EBM in order to achieve any level of autonomy without mains power. Connect any Battery
Boxes in a cascade as shown in the figure below:
1.
CONNECTION: Use 3 cables with 10 mm
2
section (Earth, +, N and -)
2. Connect the wires to the relative terminals, following exactly the instructions given below:
For 9E6Ki, 9E10Ki, 9E10KiXL
a -
Make sure that the fuse holder of the external battery box is open.
b -
Connect the earth (PE) wire to EBM’s earth (PE) screw
c -
Connect the positive (+) branch wire to EBM’s positive (+) terminal
.
d -
Connect the negative (-) branch wire to EBM’s negative (-) terminal.
The suggested tighten force is 1.6Nm.
(Detailed wiring diagram see fig 3-9~10)
Versions 9E6Ki, 9E10Ki, 9E10KiXL
Note: For 9E15Ki, 9E20Ki, 9E20KiXL EBM wiring connection, you should check the 9EEBM manual in EBM
package.
Fig.3-8 EBM terminal view (Fuse for 9E6Ki,
9E10Ki, 9E10KiXLwithout Neutral)
Fig.3-9 EBM terminal connection for 9E6Ki,
9E10Ki, 9E10KiXL With Single EBM
Fig.3-10 EBM terminal connection for 9E6Ki,
9E10Ki, 9E10KiXL With Mutliple EBM