Eaton 9E UPS (20–30 kVA, 208/220V) Generation 3 Installation and Operation Manual P-164000301—Rev 1
www.eaton.com/powerquality
7-1
Chapter 7
Communication
This chapter describes the communication features of the Eaton 9E UPS. For terminal wiring information, see
paragraph 3.2.3 and paragraph 4.11. For location of the customer interface panel and terminals, see Figure 4-10
and Figure 4-11.
7.1
Mini-Slot Cards
The Eaton 9E UPS has two standard, factory-installed Mini-Slot communication bays. See Figure 4-10 for bay
locations. The UPS is compatible with the following Mini-Slot cards (see Figure 7-1):
l
Network Management Card and Modbus/Jbus – provides remote monitoring through a Web browser
interface, e-mail, and a network management system (NMS) using SNMP and connects to a twisted-pair
Ethernet (10/100BaseT) network. The card also provides direct integration of UPS information (meters and
status) to a Building Management System (BMS) using the Modbus RTU protocol.
l
Network Management Card – provides remote monitoring through a Web browser interface, e-mail, and a
network management system (NMS) using SNMP and connects to a twisted-pair Ethernet (10/100BaseT)
network.
l
Relay Card – MS – two types of interfaces via a DB9 connector are available with this card. Dry contact
mode provides a simple way to transmit UPS information to an alarm system, PLC, or computer system via
dry relay contacts. The transmitted information is load powered, load on bypass, load on battery, load on
utility, battery fault, and low battery. RS232 mode provides an RS232 interface for connection to a PC or to a
UPS Control display unit. Jumpers are used to select the interface (contacts or RS232).
LAN and telephone drops for use with Mini-Slot connectivity cards must be supplied by facility planners or the
customer.
For installation, setup, and operation of a Mini-Slot card, refer to the instructions supplied with the Mini-Slot
card. For additional assistance, contact an Eaton service representative (see paragraph 1.7).
Figure 7-1. Optional Mini-Slot Cards
7.2
Building Alarm Monitoring
This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or
overtemperature alarms. The customer interface terminals for external connections are located inside the UPS.
Use twisted-pair wires for each alarm input and common.
The building alarms can be programmed to display the alarm functional name.
NOTE
Only one Network Management Card or Network Management Card and Modbus/
Jbus can be used at one time.
Relay Card – MS
Network Management Card
Network Management Card and
Modbus/Jbus
Summary of Contents for 9E
Page 1: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Page 2: ......
Page 3: ...Eaton 9E UPS 20 30 kVA 208 220V Generation 3 Installation and Operation Manual ...
Page 21: ...Section 1 Installation ...
Page 22: ......
Page 65: ...Section 2 Operation ...
Page 66: ......
Page 113: ......
Page 114: ... P 164000301 1 P 164000301 1 ...