15 

 

Notice:

 It is required to install an  external  isolating device against current 

backfeed  between  Mains  input  and  UPS.  After  the  device  is  installed,  it 

must  add  a  warning  label  with  the  following  wording  or  the  equivalent  on 

the  external  AC  contactor:  RISK  OF  VOLTAGE  BACKFEED.  Isolate  the 

UPS  before  operating  on  this  circuit,  then  check  for  hazardous  voltage 

between  all  terminals.  The  current  rating  of  T  -  AC  contactor  should  be 

more than 1.3 times of UPS capacity 

 

 

MAIN INPUT

UPS

B

Q

T

L

N

B      coil remote switch
Q      input main switch
T       AC contactor
L       line input
N      neutral

      

 

 
 
 
 

MAIN INPUT

UPS

B

Q

T

L1

L2

L3

N

B      coil remote switch
Q      input main switch
T       AC contactor
L1 L2 L3  line input
N       neutral

 

 

Fig.3-2 Typical external isolating device installation 

 

 

3.3.2 UPS Wiring Connection 

 

To  make  the  mains  power  and  load  connections,  follow  the  instructions 
below: 

Single phase input 

Three phase input 

Summary of Contents for 9E20K-TH

Page 1: ...powerquality eaton com Eaton 9E 6 20kVA...

Page 2: ...2 Presentation 5 2 1 Model List 5 2 2 Electrical structure 5 2 3 UPS views 7 3 Installation 12 3 1 Unpacking 12 3 2 Package content 13 3 3 Connection 13 4 OPERATION 24 4 1 Display and Buttons 24 4 2...

Page 3: ...disconnect device shall be incorporated in the building installation wiring for permanently connected equipment The UPS generates hazardous electric voltages inside it even when the input and or batte...

Page 4: ...leaks of liquid or a white powder residue Make sure that no water liquid in general and or other foreign matter gets inside the UPS Under hazardous conditions turn off the UPS at the 1 0 main power s...

Page 5: ...4 Level 4 Surge IEC EN 61000 4 5 Level 4 CS IEC EN 61000 4 6 Level 3 MS IEC EN 61000 4 8 Level 3 Voltage Dips short interruptions and voltage variations IEC EN 61000 4 11 Warning This is a product for...

Page 6: ...4 1 3 Special Symbols The following are examples of symbols used on the UPS or accessories to show you the important information...

Page 7: ...Combo 0 8 230V 220 240 9E15Ki 15kVA 12kW Combo 0 8 230V 220 240 9E20Ki 20kVA 16kW Combo 0 8 230V 220 240 9E20KiXL 20kVA 16kW Combo 0 8 230V 220 240 9EEBM180 For 9E6Ki 180V 9EEBM240 For 9E10Ki 9E10KiX...

Page 8: ...nternal power Charger Battery Input Switch Bypass Maintain Switch Output Switch Main power wiring 9E15Ki 9E20Ki 9E20KiXL INPUT OUTPUT N L N L2 L1 L3 Input filter AC DC DC AC Output filter Internal pow...

Page 9: ...7 2 3 UPS views 2 3 1 UPS Front view Display Multipurpose buttons Wheels front wheels swivel and can be locked fixed rear wheels...

Page 10: ...8 2 3 2 UPS Rear view 9E6Ki With backpanel cover 9E6Ki Without backpanel cover...

Page 11: ...ommunication port Input switch RS232 communication port and contacts Cover for terminals Slot for optional communication card Fuse Cooling fan s Terminals for I O cable connection refer to related sec...

Page 12: ...ut backpanel cover RS232 communication port and contacts Input switch USB communication port Cover for terminals Slot for optional communication card Terminals for I O cable connection refer to relate...

Page 13: ...2 3 3 EBM Rear view Fuse Cover for terminals Tie wrap hold down Wheels front wheels swivel and can be locked fixed rear wheels Terminals for I O cable connection refer to related section Earthing scre...

Page 14: ...upward and take out front PE form 4 Put the wood board removed at step2 as figure showed Make sure that the slide rests firmly against the pallet so it remains in place during unloading operations Pul...

Page 15: ...s Warning Installation must be performed by qualified personnel The first connection to perform is the protective conductor earth cable which must be connected to the screw marketed The UPS when inser...

Page 16: ...A Three phase Type B The neutral arrangements are altered only if there is an isolating transformer or when the UPS operates with a neutral that is disconnected upstream In any case avoid connecting t...

Page 17: ...hazardous voltage between all terminals The current rating of T AC contactor should be more than 1 3 times of UPS capacity MAIN INPUT UPS B Q T L N B coil remote switch Q input main switch T AC contac...

Page 18: ...ide Fig 3 3 Wiring connection Single phase version 9E6Ki only 4 SINGLE PHASE CONNECTION 9E6KI use 3 cables with cross section 6 mm 2 EARTH N and L for the input and 3 cables with cross section 6 mm 2...

Page 19: ...ase connection 4 SINGLE PHASE CONNECTION 9E10KI 9E10KIXL use 3 cables of cross section 10 mm 2 EARTH N and L for the input and 3 cables of cross section 10 mm 2 for the output EARTH N and L SINGLE PHA...

Page 20: ...ire to terminal 1 Output line a Connect the earth wire to screw B b Connect the neutral wire to terminal 5 c Connect the live wire to terminal 6 R E P O a The REPO connection between terminal 7 and 8...

Page 21: ...ONNECTION 9E20KI 9E20KIXL Use 2 cables of cross section 6 mm 2 L2 and L3 and 3 of cross section 25 mm 2 EARTH N L1 for the input N B L1 and N are of greater cross section because in bypass operation t...

Page 22: ...gency if the stop device is used the REPO control is closed and the UPS goes into stand by mode and the load is completely disconnected Attention before restarting the UPS reset the stop device The ci...

Page 23: ...into the round hole Then pull out the screw driver Connect the two wires of the cable to terminals 5 and 6 for version 9E6Ki 7 and 8 for versions 9E10Ki 9E10KiXL 9E15Ki 9E15KiXL 9E20Ki 9E20KiXL to be...

Page 24: ...he relative terminals following exactly the instructions given below For 9E6Ki 9E10Ki 9E10KiXL a Make sure that the fuse holder of the external battery box is open b Connect the earth PE wire to EBM s...

Page 25: ...E15Ki 9E20Ki 9E20KiXL EBM wiring connection you should check the 9EEBM manual in EBM package Fig 3 10 EBM terminal connection for 9E6Ki 9E10Ki 9E10KiXL With Mutliple EBM Fig 3 9 EBM terminal connectio...

Page 26: ...he buzzer will beep once then the UPS system will be turned on Turn off If the UPS is in line battery HE or battery test mode press 3s the buzzer will beep once then the UPS will be turned off Transfe...

Page 27: ...Inverter Green It indicates that the inverter is OK and the load is supplied from the inverter Note After UPS power on all LEDs will be lightened for 2 seconds and then turn to normal status When UPS...

Page 28: ...bypass One beep per 1s Note buzzer alarm can be enable disable by function button if buzzer alarm is disabled all present alarm is muted except that the button press still has a tick beep Buzzer alar...

Page 29: ...nput It indicates information for input Load It indicates information for load Battery It indicates information for battery Load level It indicates the load level Load border will flash if the load is...

Page 30: ...uously for more than 2 second the buzzer will beep once UPS starts to turn on A few seconds later the UPS turns into Line mode If the mains power is abnormal the UPS will transfer to Battery mode with...

Page 31: ...S will transfer to maintenance bypass mode Switch off the input and output switch before doing maintenance on the UPS To transfer the UPS back to normal mode switch on the input and output switch and...

Page 32: ...2 or USB communication cable to the serial or USB port on the computer 2 Connect the other end of the communication cable to the RS232 or USB communication port on the UPS The UPS can now communicate...

Page 33: ...nformation Modbus MS card has connection to Modbus protocol in addition to network management Relay MS card has isolated dry contact Form C relay outputs for UPS status Utility failure Battery low UPS...

Page 34: ...S IS IN Standby mode Press the ON button on the front panel to power the loads THE UPS IS OPERATING FROM THE BATTERY DESPITE THE PRESENCE OF MAINS VOLTAGE THE INPUT VOLTAGE IS OUTSIDE THE PERMITTED TO...

Page 35: ...301 F304 F002 THE UPS IS MALFUNCTIONING If possible disconnect the power to the load switch the UPS off and back on again if the problem occurs again call the support centre THE DISPLAY SHOWS THE CODE...

Page 36: ...ormally preceded by an alarm signal and their scale leads to the power off of the inverter and the load being powered by the bypass line CODE DESCRIPTION F002 UPS Fault F004 Dissipator over temperatur...

Page 37: ...240 Frequency Hz Selectable 50 60 or auto sensing Nominal power VA 6000 10000 15000 20000 Nominal power W 4800 8000 12000 16000 Overload 105 load 110 Bypass line available activates the bypass after...

Page 38: ...09 350 x 706 x 818 Weight kg 68 8 86 29 XL 147 160 48 5 XL Operating Temperature 0 o C to 40 o C Operating humidity 0 95 no condensing Altitude Up to 1 000 meters above sea level with 10 derating per...

Page 39: ...37 614 06847 05...

Reviews: