UPS Installation Plan and Unpacking
3-8
Eaton 9EHD UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
Table 3-6. UPS External Power Cable Terminations for the Eaton 9EHD 80-200 kVA
NOTE
Callout letters
A
,
B
,
C
, and
D
map to Figure 5-5.
Table 3-7. Recommended Input Circuit Breaker Ratings
Circuit Breaker Rating
UPS Model
Load Derating
400V
I2T
9EHD-33-80
80% Derated
153A
100% Rating
123A
9EHD-33-100
80% Derated
192A
100% Rating
154A
9EHD-33-150
80% Derated
290A
100%Rating
232A
9EHD-33-200
80% Derated
386A
100% Rating
309A
CAUTION
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table 3-7 in accordance with local regulations.
Terminal
Function
Terminal
Function
Bus landing
Tightening Torque
Nm (lb in)
Screw Size and Type
80kVA/100kVA/150kVA/200kVA
AC Input to UPS
Rectifier
L1
Phase A
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L2
Phase B
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L3
Phase C
M8 bolt mounting
24 (212)
50.24 mm²(M6)
N
Neutral
M8 bolt mounting
24 (212)
50.24 mm²(M6)
AC Input to Bypass
L1
Phase A
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L2
Phase B
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L3
Phase C
M8 bolt mounting
24 (212)
50.24 mm²(M6)
N
Neutral
M8 bolt mounting
24 (212)
50.24 mm²(M6)
AC Output to Critical
Load
L1
Phase A
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L2
Phase B
M8 bolt mounting
24 (212)
50.24 mm²(M6)
L3
Phase C
M8 bolt mounting
24 (212)
50.24 mm²(M6)
N
Neutral
M8 bolt mounting
24 (212)
50.24 mm²(M6)
DC Input from External
Battery
+
Battery (+)
M8 bolt mounting
24 (212)
50.24 mm²(M6)
–
Battery (-)
M8 bolt mounting
24 (212)
50.24 mm²(M6)
Customer Ground
M8 bolt mounting
24 (212)
50.24 mm²(M6)