Eaton 9EHD UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
9-1
Chapter 9 Product Specifications
9.1 Model Numbers
The UPS is housed in a free-standing cabinet with safety shields behind the door. The UPS is available in
50 or 60 Hz with various output power ratings.
Models
Power Rating
Frequency
9EHD-80
80 kVA
50/60 Hz
9EHD-100
100 kVA
50/60 Hz
9EHD-150
150 kVA
50/60 Hz
9EHD-200
200 kVA
50/60 Hz
9.2 Specifications
The following sections detail the input, output, environmental, and battery specifications for the UPS.
Operating Input Voltage
380/400/415 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See Table 3-5.
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801
4
Battery Voltage
480 Vdc
Battery Charging Capacity
40A maximum at any load up to100% load for 80 KVA UPS
40A maximum at any load up to100% load for 100 KVA UPS
80A maximum at any load up to100% load for 150 KVA UPS
120A maximum at any load up to100% load for 200 KVA UPS