Product Specifications
9-2
Eaton 9EHD UPS (80-200 kVA, 380/400/415V) Installation and Operation Manual
9.2.2 UPS Output
UPS Output Capacity
100% rated current
Output Voltage Regulation
± 1% (10% to 100% load)
Nominal Output Voltage
380 Vac, 400 Vac and 415 Vac nominal
Output Voltage Harmonic Content
2% maximum THD (linear load)
5% maximum THD (nonlinear load)
Output Current
See Table 3-5.
Output Voltage Balance
< 2% for 100% maximum load imbalance (linear load)
Output Voltage Phase
Displacement
< 2.5
°
for 100% maximum load imbalance (linear load)
Frequency Regulation
0.1 Hz free running
Synchronous to Bypass
± 4 Hz (default setting)
Frequency Slew Rate
3 Hz per second (default setting)
Load Compatibility
0.9 pF Leading
0.7 pF Lagging
Overload Capability
≦
125% for 10 minutes
≦
150 % for 1 minutes
≧
150% for 150 milliseconds
9.2.3 UPS Environmental
Operating Temperature
0 to 40
°
C (32 to 104
°
F) without derating. The recommended operating
temperature is 25
°
C (77
°
F).
Operating Altitude
Maximum 1000m (3300 ft) at 30
°
C without derating
Storage Temperature
-
15 to +55
°
C, excluding batteries (prolonged storage above 40
°
C causes
rapid battery self-discharge)
Relative Humidity (operating and
storage)
5% to 95% maximum noncondensing
Acoustical Noise
Less than or equal to 65 dB (80-1
0
0 kVA) and 70dB (1
5
0-200 kVA) at a
1m distance, per ISO 7779
EMC
Meets IEC 62040-2 C3