CAUTION
If battery systems are located in the same room as the UPS, the battery manufacturer's
environmental requirements should be followed if they are more stringent than the UPS
requirements. Operating temperatures above the recommended range will result in decreased
battery life and performance, and may reduce or void the battery warranty.
The UPS ventilation requirements are shown in Table 3-4.
Table 3-4 air Conditioning or Ventilation requirements during full load operation
model
rating
Input/output Voltage
Heat rejection
BTu/hr x1000 (kg-cal/hr)
Eaton 9EHD-31-40/20
20 kVA
380/220 230/230 240/240
4.62(1165)
Eaton 9EHD-33-40/20
380/380 400/400 415/415
Eaton 9EHD-31-40/30
30 kVA
380/220 230/230 240/240
6.94(1750)
Eaton 9EHD-33-40/30
380/380 400/400 415/415
Eaton 9EHD-31-40/40
40 kVA
380/220 230/230 240/240
9.24(2330)
Eaton 9EHD-33-40/40
380/380 400/400 415/415
Eaton 9EHD UPS (20-40 kVA, 380/400/415V) Installation and Operation Manual